¿Hablamos?
Caja aislante Eaton CI-K3-125-TS
Eaton · Moeller

Caja aislante Eaton CI-K3-125-TS

SKU: EATON-CI-K3-125-TS

Caja aislante Eaton modelo CI-K3-125-TS.

$808.30
Sin stock
1
Solicitar cotización

Descripción técnica

**Caja aislante Eaton CI-K3-125-TS** Caja aislante Eaton modelo CI-K3-125-TS. ### Descripción del fabricante 206884 - Eaton Moeller® series CI-K Insulated enclosure, HxWxD=200x120x125mm, +mounting rail **Entrega estimada:** 10 a 15 días hábiles (bajo pedido). Fuente: [Eaton (sitio oficial)](https://www.eaton.com/gb/en-gb/skuPage.206884.html)

Categoría: Potencia y control de motores

Especificaciones

Especificaciones técnicas
General
Model CodeCI-K3-125-TS
Largo125 mm
Alto221 mm
Ancho120 mm
Peso0.61 kg
CertificacionesDIN EN 62208 UL94: VO/1.5 mm thickness IEC/EN 60529 IEC 60068-2-11 UL94: HB
Catalog NotesLamp indicator L‐… can be mounted in base knock-out M20/M25
TipoBasic enclosure
FeaturesUV resistance beneath protective shield Halogen free
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistanceMeets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effectsMeets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiationPlease enquire
10.2.5 LiftingNot applicable.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard's requirements.
10.3 Degree of protection of assembliesMeets the product standard's requirements.
10.4 Clearances and creepage distancesMeets the product standard's requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder's responsibility.
10.8 Connections for external conductorsIs the panel builder's responsibility.
10.9.2 Power-frequency electric strengthIs the panel builder's responsibility.
10.9.3 Impulse withstand voltageIs the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating materialMeets the product standard's requirements.
Fitted with:Mounting rail to IEC/EN 60715 Control cable entry
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78
Enclosure materialPlastic 1 Ω x 10¹³ (Surface resistance to IEC 60093)
Ambient operating temperature - max70 °C
Ambient operating temperature - min-25 °C
Equipment heat dissipation, current-dependent Pvid0 W
Heat dissipation capacity Pdiss21.5 W
Heat dissipation per pole, current-dependent Pvid0 W
Mounting depth93 mm
Mounting weight capacity - max0.85 kg